Thermal insulation performance is governed by physics, not brand prestige. When you evaluate a building envelope design or an EKR energy-efficiency project, the thermal conductivity coefficient (lambda, λ) and the installed thickness decide whether the building meets the required U-value.
Core thermal metrics explained
- Thermal conductivity (λ, W/mK): how well a material conducts heat. A lower value means better insulation per millimetre of thickness.
- Thermal resistance (R = d / λ, m²K/W): the insulating capability of a given layer thickness (d in metres). Higher R means better insulation.
- Overall heat transfer coefficient (U = 1 / R_total, W/m²K): the rate of heat transfer through a complete assembly. Lower U means less heat loss.
Practical calculation: 25 cm ODE Starflex glass wool
For attic floor insulation:
- ODE Starflex glass wool thermal conductivity: λ = 0.039 W/mK
- Installed thickness: 25 cm (0.25 m), typically laid as 2 × 12.5 cm staggered layers
- Thermal resistance of the insulation layer: R = 0.25 / 0.039 = 6.41 m²K/W
- Resulting thermal transmittance through the insulation layer alone: U ≈ 0.156 W/m²K
Add the interior and exterior surface resistances (Rsi + Rse) and the ceiling structure to get the figure for the whole assembly. The target U-value is set by the project's energy calculation, not by this article.
EuConX Iso Kft. supplies factory-direct ODE Starflex glass wool with CE marking, EUCEB certification and the EPD (EPD-IES-0030984:001). Those certificates belong to the producer, ODE. The material specification of the 25 cm build-up and why contractors choose ODE Starflex give more detail. For a planning estimate, try the calculator.